PHASE FAILURE DEVICE(DIN RAIL MOUNT) FKR2T-DIN

Code: 309-004232310

KAEL/TURKEY

In three phase systems, when all phases are in correct order and phases are balanced, Normal LED turns on and the relay is energized. Missing Phase : When at least one of phases L1, L2, L3 is missing, phase off LED turns on and relay de-energizes its contact. Phase Sequence : If the phase sequence is correct, Relay On LED turns on and relay energizes its contact. If phase order is changed, Phase Off LED turns on and relay de-energizes its contact. Phase Voltage Unbalance : Phase-phase voltage unbalance is adjusted using the knob located on the front panel of the device. If phase unbalance exceeds the adjusted limit, Phase Off LED turns on, relay deenergises its contact . Voltage Asymmetry Adjustment (Phase Unbalance)(asym.%) Phase to phase asymmetry is adjusted using the adjustment knob in the range of ±%6 .... ±%20 .
  • Power Supply:3 x 380 V AC
  • Voltage monitoring:5 ~ 15 % ( adjustable )
  • Phase loss:Yes
  • Phase sequence:Yes
  • Phase assymetry:Yes
  • Temperature control:PTC
  • Max contact current:5 A
  • Output:1 C / O
  • Dimension (mm):58 x 90 x 35
  • Package:10
  • Type:FKR2T